Reliability Assessment of Pasar Baru and Plaza Bogor Buildings

Authors

  • Muhamad Lutfi INDONESIA
  • Nurul Chayati Ibn Khaldun University of Bogor, Bogor, INDONESIA
  • Rezkia Dizha Aulia Ibn Khaldun University of Bogor, Bogor, INDONESIA
  • Siska Yusup Ibn Khaldun University of Bogor, Bogor, INDONESIA
  • Muhammad Khaerul Insan Ibn Khaldun University of Bogor, Bogor, INDONESIA

DOI:

https://doi.org/10.32832/astonjadro.v15i2.19285

Keywords:

building reliability, building functional suitability, visual observation, Non Destructive Test.

Abstract

The Pasar Baru Bogor and Plaza Bogor buildings have been in operation for decades, so it is necessary to analyze the reliability of the buildings to ensure their structural and operational conditions. This research evaluates the physical reliability of both buildings through visual observation and concrete quality testing using the method Non-Destructive Test (NDT) with the tool Hammer Test Type N. The evaluation covers five main aspects: architecture, structure, utilities and fire protection, accessibility, and building and environmental planning. The results of the research on the Pasar Baru Bogor Building show that the reliability value of the architectural aspects is 83.30%, structure 93.06%, utilities and fire protection 42.50%, accessibility 68.25%, and building and environmental planning 63.46%, with a total reliability of 64.08% which is classified as "Not Reliable." Concrete compressive strength testing shows results between 25.69 MPa and 65.81 MPa, so the structure is declared "Safe". The Plaza Bogor Building has an architectural aspect reliability value of 89.00%, structure 100%, utilities and fire protection 61.67%, accessibility 72%, and building and environmental planning 66.60%, with a total reliability of 76.66% which is categorized as "Less Reliable." Concrete compressive strength testing shows results between 23.72 MPa and 65.84 MPa, which meets structural reliability standards. Thus, the Pasar Baru Bogor Building has low reliability although the building structure is safe, while the Plaza Bogor Building has good structural reliability, but other aspects require improvement to increase reliabilitymaximum.

References

. N. Taurino and H. Wiyanto, "Building Reliability Assessment Study," 2020.

. M. P., Ibnu Herlambang Sujatmiko, "Evaluation of Physical Reliability of Building (Case Study in Sleman Regency Area)," Semesta Tek., vol. 14, no. 2, pp. 150-159, 2015, doi: 10.18196/st.v14i2.544.

]. Directorate of Strategic Infrastructure of the Ministry of Public Works and Housing, TECHNICAL AUDIT GUIDE FOR BUILDING GRANDS, 2020.

]. A. Goeritno et al., "Initial Observation: Model of Community Service by Lecturers through Independent Activities at Sekolah Aliya Bogor," Journal of Community Service, vol. 13, no. 4, pp. 594-604, 2020. [Online]. Available: http://journal.upgris.ac.id/index.php/e-dimas.

]. S. Janizar, F. Setiawan, and E. Kurniawan, "Examination of the Feasibility of Hospital Building Function," Journal of Civil Engineering Cendekia (JTSC), vol. 1, no. 1, pp. 58-67, 2020. [Online]. Available: https://doi.org/10.51988/vol1no1bulanjulitahun2020.v1i1.8.

]. M. Lutfi et al., "The Reliability Level of Women's Dormitory Building Ibn Khaldun University Bogor," Astonjadro, vol. 13, no. 1, pp. 1-011, 2024. [Online]. Available: https://doi.org/10.32832/astonjadro.v13i1.

]. M. Lutfi and A. Maulana, "Analysis of Structure Reliability of Uthman Bin Affan Building (Case Study: Aliya Bogor Integrated Islamic School)," Astonjadro, vol. 9, no. 2, p. 93, 2020. [Online]. Available: https://doi.org/10.32832/astonjadro.v9i2.3111.

]. M. Lutfi and E. Rusandi, "Evaluation of Shophouse Building Structure Due to Additional Roof Load in the Form of Mini Tower," Astonjadro, vol. 8, no. 2, p. 87, 2020. [Online]. Available: https://doi.org/10.32832/astonjadro.v8i2.2790.

]. M. Lutfi and B. N. Syaifullah, "Feasibility Analysis of the Bogor Sukasari Market Building through the Building Functioning Approach," Astonjadro, vol. 9, no. 1, p. 14, 2020. [Online]. Available: https://doi.org/10.32832/astonjadro.v9i1.2726.

]. Perumda Pasar Pakuan Jaya, Pasar Baru Bogor, 2017. [Online]. Available: https://pasarpakuanjaya.co.id/post/read/97347979831837222316/pasar.baru.bogor. [Accessed: 28-Sep-2024].

]. T. I. Praganimrum, N. L. M. A. M. Pradnyadari, and P. O. M. Firanthi, Building Reliability Analysis (Case Study: Rectorate Building of Mahasaraswati University Denpasar), 2023. [Online]. Available: http://journal.unmasmataram.ac.id/index.php/GARA.

]. Government Regulation No. 36/2005 on the Implementation Regulation of Law No. 28/2005 on Building.

]. Regulation of the Minister of Public Works and Housing No. 29/PRT/M/2006 on Guidelines for Technical Requirements for Buildings.

]. Minister of Public Works Regulation No. 30/PRT/M/2006 on Technical Guidelines for Facilities and Accessibility.

]. Regulation of the Minister of Public Works No. 24/PRT/M/2008 on Technical Guidelines for the Maintenance and Care of Buildings.

]. Regulation of the Minister of Public Works No. 26/PRT/M/2008 on Technical Requirements for Fire Protection Systems in Buildings and Environments.

]. Bogor Mayor Regulation Number 23 Year 2016 on Building Setback Lines in Bogor City.

]. Regulation of the Minister of Public Works and Public Housing No. 27/PRT/M/2018 on Certificate of Building Functioning.

]. Government Regulation Number 16 of 2021 concerning Building.

]. SNI 2847-2019 on Structural Concrete Requirements for Building.

]. SNI 03-4430-1997 on Method of Testing the Compressive Strength of Concrete Structural Elements with Type N and NR Concrete Hammers.

]. Law Number 28 Year 2002 on Building.

Published

2026-05-24

How to Cite

Lutfi, M., Chayati, N., Aulia, R. D., Yusup, S., & Insan, M. K. (2026). Reliability Assessment of Pasar Baru and Plaza Bogor Buildings. ASTONJADRO, 15(2), 383–393. https://doi.org/10.32832/astonjadro.v15i2.19285

Issue

Section

Articles